آخر الأخبار

جاري التحميل ...

Faults and Abnormal Operating Conditions

Protective Relaying (Part2)
1.1 Shunt Faults (Short Circuits)
       When the path of the load current is cut short because of breakdown of insulation, we say that a 'short circuit' has occurred. The insulation can break down for a variety of reasons, some of which are listed in Section 1.2. Figure 1.1 shows a single line-to-ground fault on a transmission line due to flashover of spark gap across the string insulator.
Figure 1  Single line-to-ground fault due to flashover of insulator string.
       Such faults due to insulation flashover are many times temporary, i.e. if the arc path is allowed to deionize, by interrupting the electrical supply for a sufficient period, then the arc does not re-strike after the supply is restored. This process of interruption followed by intentional re-energization. In low-voltage systems up to three reclosure are attempted, after which the breaker is locked out. The repeated attempts at reclosure, at times, help in burning out the object which is causing the breakdown of insulation. The reclosure may also be done automatically. In EHV systems, where the damage due to short circuit may be very large and the system stability at stake, only one reclosure is allowed.
       At times the short circuit may be total (sometimes called a dead short circuit), or it may be a partial short circuit. A fault which bypasses the entire load current through itself, is called a metallic fault. A metallic fault presents a very low, practically zero, fault resistance. A partial short circuit can be modelled as a non-zero resistance (or impedance) in parallel with the intended path of the current. Most of the times, the fault resistance is nothing but the resistance of the arc that is formed as a result of the flashover. The arc resistance is highly nonlinear in nature. Early researchers have developed models of the arc resistance. One such widely used model is due to Warrington, which gives the arc resistance as :
       where
             S is the spacing in feet
             u is the velocity of air in mph
             t is the time in seconds
             I is the fault current in amperes.
1.2 Causes of Shunt Faults
       Shunt faults are basically due to failure of insulation. The insulation may fail because of its own weakening, or it may fail due to overvoltage. The weakening of insulation may be due to one or more of the following factors:
  • Ageing 
  • Temperature
  • Rain, hail, snow
  • Chemical pollution
  • Foreign objects
  • Other causes
       The overvoltage may be either internal (due to switching) or external (due to lightening).
1.3 Effects of Shunt Faults
       If the power system just consisted of isolated alternators feeding their own loads, then the steady-state fault currents would not be qpch of a concern. Consider an isolated turboalternator with a three-phase short circuit on its terminals as shown in Figure.2. Assuming the internal voltage to be 1 p.u. and a value of synchronous impedance, Xd = 2 p.u., the steady-state short-circuit current would only be 0.5 p.u. which is too small to cause any worry. However considering subtransient impedance, Xd'' = 0.1, the subtransient current would be 10 p.u. We must not, however, forget that in an interconnected power system all the generators (and even motors) will contribute towards the fault current, thus building up the value of the fault current to couple of tens of times the normal full-load current.
Figure .2 Isolated generator experiences a three-phase fault.
       Faults, thus, cause heavy currents to flow. If these fault currents persist even for a short time, they will cause extensive damage to the equipment that carry these currents. Over-currents, in general, cause overheating and attendant danger of fire. Overheating also causes deterioration of the insulation, thus weakening it further. Not SO apparent is the mechanical damage due to excessive mechanlcal forces developed during a over-current. Transformers are known to have suffered mechanical damage to their windings, due to faults. This is due to the fact that any two current-carrying conductors experience a force. This force goes out of bounds during faults, causing mechanical distortion and damage.
       Further, in an interconnected system, there is another dimension to the effect of faults. The generators in an interconnected power system must operate in synchronism at all instants. The electrical power output from an alternator near the fault drops sharply. However the mechanical power input remains substantially constant at its prefault value. This causes the alternator to accelerate. The rotor angle 6 starts increasing. Thus, the alternators start swinging with respect to each other. If the swing goes out of control, the alternators will have to be tripped out. Thus, in an interconnected power system, the system stability is at stake. Therefore, the faults need to be isolated as selectively and as speedily as possible.

Sponsored links :

about author

hamada i'm hamada rageh electrical power engineer my talent to write articles about electrical engineering and i depend on google books site to write my articles

التعليقات


اتصل بنا

إذا أعجبك محتوى مدونتنا نتمنى البقاء على تواصل دائم ، فقط قم بإدخال بريدك الإلكتروني للإشتراك في بريد المدونة السريع ليصلك جديد المدونة أولاً بأول ، كما يمكنك إرسال رساله بالضغط على الزر المجاور ...

جميع الحقوق محفوظة

your electrical home