آخر الأخبار

جاري التحميل ...

Classification of Shunt Faults

Protective Relaying (Part3)
1.1 Phase Faults and Ground Faults
       Those faults, which involve only one of the phase conductors and ground, are called ground faults. Faults involving two or more phase conductors, with or without ground, are called phase faults.
        Power systems have been in operation for over a hundred years now. Accumulated experience shows that all faults are not equally likely. Single line to ground faults (L-G) are the most likely whereas the fault due to simultaneous short circuit between all the three lines, known as the three-phase fault (L-L-L), is the least likely. This is depicted in Table 1.
Table 1.Fault statistics with reference to type of fault
       Further, the probability of faults on different elements of the power system are different. The transmission lines which are exposed to the vagaries of the atmosphere are the most likely to be subjected to faults. Indoor equipment is least likely to be subjected to faults. The fault statistics is shown in Table .2.
Table .2   Fault statistics with reference to power system elements
       The severity of the fault can be expressed in terms of the magnitude of the fault current and hence its potential for causing damage. In the power system, the three-phase fault is the most severe whereas the single line-to-ground fault is the least severe.
1.2 Phasor Diagram of Voltages and Currents During Various Faults
       A fault is accompanied by a build-up of current, which is obvious. At the same time there is a fall in voltage throughout the power system. If the fault is a metallic fault, the voltage at the fault location is zero. The voltage at the terminals of the generator will also drop, though not drastically. If the source is ideal, there will be no drop in voltage at the generator terminals. Normally the relay is away from the fault location. Thus, as seen from the relay location, a fault is characterized by a build-up of current, and to a certain extent, collapse of voltage.
       Figure 1. depicts various ground faults as well as phase faults.
Fig. 1 Various ground faults and phase faults
       Figure 2 depicts a radial power system with a fault near the remote end of the transmission line. It can be seen from the phasor diagram that the voltage at the relay location during fault is less in magnitude than that during the pre-fault condition and also lags its pre-fault value. In order not to clutter the diagram, only phase a voltage is shown. In Figure 2, the distortion in voltages during all the 11 shunt faults are considered.
Fig 3  Fall of voltage at the relay location shown on single line diagram of a three-phase system.
Figure 3   Voltages at the relay location during various faults

1.3 Series Faults
       Series faults are nothing but a break in the path of current. Normally such faults do not result into catastrophes except when the broken conductor touches other conductor or some grounded part. It is observed in practice that most of the open conductor faults sooner or later develop into some or the other short-circuit fault. However, there are some instances where an open circuit can have dangerous consequences For example, the secondary circuit of a current transformer and the field circuit of a dc machine if open circuited, can have dangerous consequences.

Sponsored links :

about author

hamada i'm hamada rageh electrical power engineer my talent to write articles about electrical engineering and i depend on google books site to write my articles

التعليقات


اتصل بنا

إذا أعجبك محتوى مدونتنا نتمنى البقاء على تواصل دائم ، فقط قم بإدخال بريدك الإلكتروني للإشتراك في بريد المدونة السريع ليصلك جديد المدونة أولاً بأول ، كما يمكنك إرسال رساله بالضغط على الزر المجاور ...

جميع الحقوق محفوظة

your electrical home