Phasor Diagrams for Transformer on Load

Phasor Diagrams for Transformer on Load
       Consider a transformer supplying the load as shown in the Fig. 1.
Fig. 1
       The various transformer parameters are,
                        R1 = Primary winding resistance
                        X1 = Primary leakage reactance
                        R2 = Secondary winding resistance
                        X2 = Secondary leakage reactance
                         ZL = Load impedance
                         I1= Primary current
                          I2 = Secondary current = IL = Load current 
now                    Ī1 = Īo + Ī2'
where                 Io = No load current 
                           I2'= Load component of current decided by the load
                               = K I2 where K is transformer component
       The primary voltage V1 has now three components,
1. -E1, the induced e.m.f. which opposes V1
2. I1 R1, the drop across the resistance, in phase with I1
3. I1 X1, the drop across the reactance, leading I1 by 90o

       The secondary induced e.m.f. has also three components,
 1. V2, the terminal voltage across the load
2. I2 R2, the drop across the resistance, in phase with I2
3. I2 X2, the drop across the reactance, leading I2 by 90o

       The phasor diagram for the transformer on load depends on the nature of the load power factor. Let us consider the various cases of the load power factor.

1.1 Unity power factor load, cosΦ2 = 1
       As load power factor is unity, the voltage V2 and I2 are in phase. Steps to draw the phasor diagram are,
1. Consider flux Φ as reference
2. E1 lags Φ by 90o. Reverse E1 to get -E1.
3. E1 and E2 are inphase
4. Assume V2 in a particular direction
5. I2 is in phase with V2.
6. Add I2 R2 and I2 X2 to to get E2.
7. Reverse I2 to get I2'.
8. Add Io and I2' to get I1.
9. Add I1 R1 and to -E1 to get V1.
       Angle between V1 and I1 is Φ1 and cosΦ1 is primary power factor. Remember that I1X1 leads I1 direction by 90o and I2 X2 leads I2 by 90o as current through inductance lags voltage across inductance by 90o. The phasor diagram is shown in the Fig.2
Fig. 2  Phasor diagram for unity power factor load

Lagging Power Factor Load, cos Φ2
       As load power factor is lagging cosΦ2, the current I2 lags V2 by angle Φ2. So only changes in drawing the phasor diagram is to draw I2 lagging V2 by Φ2 in step 5 discussed earlier. Accordingly direction of I2 R2, I2 X2, I2', I1, I1 R1 and I1X1 will change. Remember that whatever may be the power factor of load, I2X2 leads I2 by 90o and I1X1 leads I1 by 90o.
       The complete phasor diagram is shown in the Fig. 3.
Fig.  3  Phasor diagram for lagging power factor

Loading Power Factor Load, cos Φ2
       As load power factor is leading, the current I2 leads V2 by angle Φ2. So change is to draw I2 leading Iby angle Φ2. All other steps remain same as before. The complete phasor diagram is shown in the Fig. 4
Fig. 4  Phasor diagram for leading power factor

Sponsored links :

  1. Very good information!!!! Thank you, Erik Arckens

    ReplyDelete
  2. there are two inductances on primary side one is that of Py winding and other due to leakage reactance. lenz's law is applicable on both inductors.i.e there should be -ve sign with E1 as well as I1X1 drop. but we have used with only E1 not with the other inductor.please explain with very basic concepts so that I can get the idea.further with applied signs both should be voltage drop across the inductor and should have same sign?

    ReplyDelete
  3. please post the picture of phasor diagram of ideal transformer with capacitive load

    ReplyDelete
  4. This was really helpful... Thank u so much.

    ReplyDelete
  5. Please explain the expression for volt ampere and reactive volt ampere in three phase system

    ReplyDelete
  6. Life is full of many challenges. Challenges that will make you or break you depending on how you handle it. Visit my site for more updates. God Bless to your site.

    n8fan.net

    www.n8fan.net

    ReplyDelete
  7. Sir, In the practical transformer case, what is criteria for drawing the V2 phasor? How much angle the V2 phasor is lagging or leading the E2 phasor?

    ReplyDelete
    Replies
    1. Sir, actually V2 is not leading or lagging by E2 because two voltages never leads or lags behind / over themself.

      Actually V2 is drawn as per our load conditions
      Let me clear....
      I2 is drawn as reference of I2'and than V2 is drawn as per the load condition. (Lagging/leading/unity).
      If our load is lagging than we draw V2 leading by I2 (or I2 lagging by V2), If our load is unity than V2 is in phase of I2 , If our load is leading than draw the V2 lagging by I2 (or I2 leading by V2). As shown in phasors.

      Delete
  8. Toroidal winding machine has included changing parameters with the support of controller unit and this is multi-reason joined controller. The structure can be changed to pass on the sensible application for focal application. So in like way, the toroidal winding machine has contained with standard stepper motor drive, DC motor drive, and power supplies in a control box. All around, this kind of winding machines has controlled for transformers. Bobbins

    ReplyDelete
  9. Another material is kool mu is sensible cost and it has demonstrate the lower loads and in a general sense goliath warm properties when related with controlled iron obsession interests. The kool mu is key use when the high flux thickness and low fixation stacks fittingly figure change circuits same as unidirectional drive application like pulse transformer and flyback transformer.toroidal transformer winding machine

    ReplyDelete
  10. The running with kind of circle winding machine is set up with spool, bobbin and some stunning materials and it would be apply specific endeavors. As a last resort, the circle winders can sorted in setting of most overwhelming and its speed levels. The turn winding machine speed levels has moved the most difficult to miss and execution.Miniature Winding

    ReplyDelete
  11. https://tubeless12.blogspot.in/2018/05/how-to-reach-allen-sankalpa-kota.html?m=1

    ReplyDelete

التعليقات


جميع الحقوق محفوظة

your electrical home