آخر الأخبار

جاري التحميل ...

  1. VandanaTransformers is a leading Transformer Manufacturing Company in Bangalore, India. we offer high quality transformers at affordable prices. Our product range includes isolation transformer, voltage transformer, auto transformer, current transformers, power isolation transformer, electric isolation transformer, high voltage current transformers, voltage isolation transformer, high voltage isolation transformer, variable auto transformer, electrical auto transformer, high voltage transformer, potential voltage transformer, toroidal current transformers and more.

    ReplyDelete
  2. Earthing transformer is usually being used in electrical substation. The main purpose is to create a neutral point in areas where earth point is not available.
    Power transformers in India | Wire harness manufacturer in India

    ReplyDelete
  3. Very Nice! Good information you shared about Earthing transformer importances and there uses in present generation. Thanks for sharing.

    ReplyDelete
  4. Great Blog! Thanks for sharing nice information about transformers and there uses.

    SMPS Transformer Manufacturer in India | Toroidal Transformer in India

    ReplyDelete
  5. Thank you for sharing such a nice blog with useful information. I would like to know more about affordable electrician.
    affordable electrician

    ReplyDelete

Earthing Transformer

       When the transformers or generators are delta connected or if the neutral points are not accessible then artificially the neutral earthing point can be created with the use of star connected earthing transformer. Such transformer has no secondary. Each phase of primary has two equal parts. There are three limbs and each limb has two windings providing opposite flux during normal condition. Such a transformer is shown in the Fig.1.
Fig. 1
       One set of windings are connected in star providing the neutral point. The other ends of this set of windings are connected to the second set of windings as shown in the Fig. 1. The directions of the currents in the two windings on each limb are opposite to each other. The small exciting current is circulated in the windings during normal operation. Under faulty condition, the transformer offers a low impedance path to the flow of zero phase sequence currents. The value of fault current is limited in some cases by the use of a resistor in series with the neutral earthing connection. This is necessary in systems with operating voltage between 2.2 KV and 3.3 KV.
       The transformers are of short time ratings in the range of 10 seconds to 1 minute. Hence the size of these transformers is small as compared to power transformers of small rating. If the earthing transformer is not available then a star-delta transformer is used.