آخر الأخبار

جاري التحميل ...

Restricted Earth Fault Protection of Generator

Generator Protection Part 6
1. Restricted Earth Fault Protection of Generator
       Generally Merz-Price protection based on circulating current principle provides the protection against internal earth faults. But for large generators, as there are costly, an additional protection scheme called restricted earth fault protection is provided.
       When the neutral is solidly grounded then the generator gets completely protected against earth faults. But when neutral is grounded through earth resistance, then the stator windings gets partly protected against earth faults. The percentage of windings protected depends on the value of earthing resistance and the relay setting.
       In this scheme, the value of earth resistance, relay setting, current rating of earth resistance must be carefully selected. The earth faults are rare near the neutral point as the voltage of neutral point with respect to earth is very less. But when earth fault occurs near the neutral point then the insufficient voltage across the fault drivers very low fault current than the pick up current of relay coil. Hence the relay coil remains unprotected in this scheme. Hence it is called restricted earth fault protection. It is usual practice to protect 85% of the winding.
       The restricted earth fault protection scheme is shown in the Fig. 1.
Fig. 1 Restricted earth fault protection

       Consider that earth fault occurs on phase B due to breakdown of its insulation to earth, as shown in the Fig. 1. The fault current If will flow through the core, frame of machine to earth and complete the path through the earthing resistance. The C.T. secondary current I flows through the operating coil and the restricted earth fault relay coil of the differential protection. the setting of restricted earth fault relay and setting of overcurrent relay are independent of each other. Under this secondary current Is, the relay operates to trip the circuit breaker. The voltage Vbx is sufficient to drive the enough fault current If when the fault point x is away from the neutral point.
       If the fault point x is nearer to the neutral point then the voltage Vbx is small and not sufficient to drive enough fault current If. And for this If, relay can not operate. Thus part of the winding from the neutral point remains unprotected. To overcome this, if relay setting is chosen very low to make it sensitive to low fault currents, then wrong operation of relay may result. The relay can operate under the conditions of heavy through faults, inaccurate C.T.s, saturation of C.T.s etc. Hence practically 15% of winding from the neutral point is kept unprotected, protecting the remaining 85% of the winding against phase to earth faults.
1.1 Effect of Earth Resistance on % of Winding Unprotected
       Let us see the effect of earth resistance on the % of the winding which remains unprotected.
       Consider the earth resistance R used to limit earth fault as shown in the Fig. 2.
Fig. 2

       The value of the resistance R limits the earth fault current.
       If the resistance R is very small i.e. the neutral is almost solidly grounded, then the fault current is very high. But high fault currents are not desirable hence small R is not preferred for the large machines.
       For low resistance R, the value of R is selected such that full load current passes through the neutral, for a full line to neutral voltage V.
       In medium resistance R, the earth fault current is limited to about 200A for full line to neutral voltage V, for a 60 MW machine.
       In high resistance R, the earth fault current is limited to about 10 A. This is used for distribution transformers and generator-transformer units.
       Now higher the value of earth resistance R, less is the earth fault current and less percentage of winding gets protected. Large percentage of winding remains unprotected.
Let                  V= Full line to neutral voltage
                        I = Full load current of largest capacity generator
                        R = Earth resistance
       The value of the resistance R is,
                         R = V/I
       And the percentage of winding unprotected is given by,

Where                Io = Maximum operating current in the primary of C.T.
       If relay setting used is 15% then Io is 15% of full load current of the largest machine and so on.
       Greater percentage of windings of small capacity machines running parallel get protected.
Example 1 : A generator is protected by restricted earth fault protection. The generator ratings are 13.2 kV, 10 MVA. The percentage of winding protected against phase to ground fault is 85%. The relay setting is such that it trips for 20% out of balance. Calculate the resistance to be added in the neutral to ground connection.
Solution : The given values,
                 VL = 13.2 kV            Rating = 10 MVA
From rating, calculate the full load current,
                  I = Rating in VA / (√3 VL) = (10x106)/(√3 x 13.2 x 103)
                     = 437.386 A
       Relay setting is 20% out of balance i.e. 20% of the rated current activities the relay.
                   I= 4387.386 x (20/100) = 87.477 A
                        = Minimum operating current
                   V = Line to neutral voltage = VL/√3
                       = (13.2 x 103)/√3 = 7621.02 V
       % of winding unprotected = 15% as 85% is protected
...                  15 = (RIo/V) x 100
...                       = ((R x 87.477)/7621.02) x 100
...                    R = 13.068 Ω
Example 2 : A star connected 3 phase, 12 MVA, 11 kV alternator has a phase reactance of 10%. It is protected by Merz-Price circulating current scheme which is set to operate for fault current not less than 200 A. Calculate the value of earthing resistance to be provided in order to ensure that only 15% of the alternator winding remains unprotected.
Solution : The given values are,
                    VL = 11 kV        Rating = 12 MVA
               Rating = √3 VL IL
...         12 x 106= √3 x 11 x 103 x IL
...                   IL = (12 x 106)/ (√3 x 11 x 103)
                         = 629.8366 A = I = rated current
                       V = VL/√3 = (11 x 103)/√3 = 6350.8529 V
      % Reactance = (IX /V) x 100
Where             X = reactance per phase
and                   I = rated current
...                  10 = (629.8366X / 6350.82529 ) x 100
...                    X = 1.0083 Ω
..Reactance of unprotected winding
                          = (% of unprotected winding) x (X)
                           = (15/100) x 1.0083
                           = 0.1512 Ω
                         v = Voltage induced in unprotected winding
                            = (15/100) x V = 0.15 x 6350.8529
                            = 952.6279 V
                          i = Fault current
                            = 200 A
                         Z = Impedance offered to the fault
                            = v/i = 952.6279/200
                            = 4.7631 Ω                        ...........(1)
                         Z = r + j (reactance of unprotected winding)
                         Z = r + j (0.1512) Ω
...                  │Z│= √(r2 + 0.15122)             .............(2)
       Equation (1) and (2),
                 4.7631 = √(r2 + 0.15122)
...             22.6875 = r2 + 0.02286
...                        r2 = 22.6646
...                         r = 4.7607 Ω
       This is the earthing resistance required

Sponsored links :

about author

hamada i'm hamada rageh electrical power engineer my talent to write articles about electrical engineering and i depend on google books site to write my articles

التعليقات


اتصل بنا

إذا أعجبك محتوى مدونتنا نتمنى البقاء على تواصل دائم ، فقط قم بإدخال بريدك الإلكتروني للإشتراك في بريد المدونة السريع ليصلك جديد المدونة أولاً بأول ، كما يمكنك إرسال رساله بالضغط على الزر المجاور ...

جميع الحقوق محفوظة

your electrical home