  1. Your blog awesome, you shared valuable information about in #Power quality in electrical system. We provide more information in Harmonic distortions is one of the most common and irritating problems in industrial environment. We need to identify the source of harmonics and suppress them for a quality supply of power. Please visit Harmonic Analysis

    ReplyDelete

Delta-Star Connection of 3-Phase Transfomer

       In this type of connection, the primary connected in delta fashion while the secondary current is connected in star fashion as shown in the Fig.1.



       The voltage on primary and secondary side can be represented on the phasor diagram as shown in the Fig. 2.

       The another way of representing the same type of connection is shown in the Fig. 3.

       The main use of this connection is to step up the voltage i.e. at the begining of high tension transmission system. It can be noted that there is a phase shift of 30° between primary line voltage and secondary line voltage as leading.
Key point : As secondary side is star connected, use of three phase, four wire system is possible.
       Thus single phase and three phase loads can be supplied with this type of connection.
Let                             VL1 = Line voltage on primary side.
                                  VL2 = Line voltage on secondary side.
                                   Vph1 = Phase voltage on primary side.
                                   Vph2 = Phase voltage on secondary side.
                                    K = Transformation ratio.
       As primary in delta connected,
                                     VL1 = Vph1
Now,                             Vph2/Vph1 = K
 ..                                  Vph2 = K Vph1
       Here secondary is connected in star
                                       VL2 = √3 Vph2
                                       VL2 = (√3 K) Vph1
                                       VL2 = (√3 K) VL1

The advantages and disadvantages with this type of connection are given below.
Advantages
  1. On primary side due to delta connection winding cross-section required is less.
  2. On secondary side, neutral is available, due to which it can be used for 3-phase, 4 wire supply system.
  3. There is no distortion due to third harmonic componenets.
  4. The windings connected on star makes it economical due to saving in cost of insulation.
  5. Large unbalanced loads can be handled without any difficulty.
Disadvantages 
Due to phase shift between primary and secondary voltages, the limitation of Star-Delta connection continues for this type of connection as well.